10.4 OUTPUT CHARACTERISTICS

Output characteristics
Power, rated:
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
neutral available
Voltage (steady state, r.m.s.), rated:
variation in normal mode / battery mode
Total harmonic distortion (THDu), 100% load, normal mode:
linear
non-linear (according to IEC 62040-3)
Total harmonic distortion, 100 % load, battery mode:
linear
non-linear (according to IEC 62040-3)
Voltage unbalance and phase displacement, 100 % load unbalance
Voltage transient and recovery time, 100% step load:
linear
non-linear (according to IEC 62040-3)
transfer normal mode --> battery mode
Frequency (steady-state), rated:
variation in normal mode (frq. Synchronized with mains)
variation in battery mode (free-running)
Max synch phase error (referred to a 360° cycle)
Max slew-rate
Nominal current (In), r.m.s. rated:
overload on inverter
fault clearing capability normal mode and battery mode for 100ms
Load power factor, rated
displacement (permissible lead-lag range)
AC / AC efficiency in normal mode, linear load:
100% load
75% load
50% load
25% load
Eco-mode efficiency, linear load
Crest – Factor (Load supported)
Static bypass
Type: automatic, static switch in each module
transfer time: inverter  bypass / bypass  inverter / in eco-mode
rated current
fault clearing capability (bypass mode) for 20 ms
overload current on bypass mode (< 25°C)
Maintenance bypass: optional on the frame
Bypass protection fuse or circuit breaker rating
04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx
Modifications reserved
UPS frame
UPS module
values
values
500
3x380/220V+N
3x400/230V+N
3x415/240V+N
± 1.5 / ± 1.5
± 2 / ± 4
725
0.5 @ 150% load,
5 @ 125% load,
20 @ 110% load
1711 (2.36xIn)
348 (2.4xIn)
(all range) 0
<1 / <5 / <6
800
10xIn
continuously @ 110% load
5x160
Unit
100
kW
3
yes
VAC
%
< 2.0
%
< 4.0
< 2.0
%
< 4.0
0
°
± 4
%
± 4
%
0
%
50/60
Hz
%
± 0.1
<2
°
1
Hz/s
145
A
min
A
1
%, s
95.6
96.0
%
96.1
95.8
≥ 99
%
3:1
ms
160
A
10xIn
A
min
A, gL fuse