Output Characteristics - ABB Conceptpower DPA 500 Operating Manual

100-500 kw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

4 Output characteristics

Conceptpower DPA 500
Power, rated:
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
neutral available
Voltage (steady state, r.m.s.), rated
Variation in normal mode / battery mode
Total harmonic distortion (THDu), 100% load, normal mode:
Linear
Non-linear
(acc. to IEC 62040-3)
Total harmonic distortion (THDu), 100% load, battery mode:
Linear
Non-linear
(acc. to IEC 62040-3)
Voltage unbalance and phase displacement,
unbalance
Voltage transient and recovery time, 100% step load:
Linear
Non-linear
(acc. to IEC 62040-3)
Transfer normal mode --> battery mode
Frequency (steady-state), rated:
Variation in normal mode
(frq. Synchronized with mains)
Variation in battery mode
(free-running)
Max synch phase error (referred to a 360° cycle)
Max slew-rate
Nominal current (In), r.m.s. rated:
Overload on inverter
Fault clearing capability normal mode and battery mode
(100ms)
Load power factor, rated
Displacement
(permissible lead-lag range)
Double conversion efficiency in normal mode, linear load:
Modifications reserved
Page 9/25
Values
500
3
yes
3x380/220V+N
3x400/230V+N
3x415/240V+N
± 1.5 / ± 1.5
< 2.0
< 4.0 %
< 2.0
< 4.0 %
0
100% load
± 4
± 4
0
50 / 60 (selectable)
± 2 / ± 4
± 0.1
<2
1
725
0.5 @ 150% load,
5 @ 125% load,
20 @ 110% load
1711 (2.36xIn)
1
(all range) 0
Unit
100
kW
-
-
VAC
%
%
%
%
%
°
%
%
%
Hz
%
%
°
Hz/s
145
A
min
348 (2.4xIn)
A
-
%, s