FT-70 Fill Level Inspector Service Manual

PLC Series Alarms

9-4
To configure your FT-70 for operation with a PLC you must
activate the PLC Series Alarms functions in the FT-70's software.
To activate the PLC Series Alarms:
1. Open dip Switch S1-5 to enter the System Configuration
2. Press Key 5 until SYSTEM DISPLAY appears and press the
Arrow Key to select CALIBRATE.
3. Press Key 5 until PLC SERIES ALARMS appears and press the
Arrow Key to select PRESENT.
4. Close Dip switch S1-5.
The PLC Series Alarm functions are now activated in the system
software. The following options will now appear in the Function
Menus. Refer to Chapter 5: System Software for information on
these functions.
• PLC Pin Assignments
• PLC Output Pulse Width
• Alarm Series Underfills
• Alarm Series Overfills
• Alarm Series Missing Lid
• Alarm Series Bulged End
• Alarm Series Down Can
• Alarm Series Dia. Missing Lid
• Alarm Series Any Other Inspections.
Industrial Dynamics Company, Ltd. © 40256-0600