Host/Modbus Port Status

Displays the character information in a Modbus serial communi-
cation string. The counters have a range of 0-255 and then reset.
• LC is the last character that was received by the FT-70.
• RX is a count of the characters received by the FT-70.
• TX is a count of the characters transmitted by the FT-70.
Pressing the Arrow Key sends the test message IDC
HOST/MODBUS TEST MESSAGE and the TX counter will
increment by 30.
For further information refer to the Serial Communication
Manual.

Modbus Message Counters

Displays the number of Modbus messages the FT-70 receives and
defines them as good, bad, or other.
• Good is the number of good messages received.
• Bad is the number of bad messages received
• Other is the number of messages received with an incorrect
Serial ID Number
For further information refer to the Serial Communication
Manual.

PLC Output Pulse Width

Defines the output pulse width of all pulsed PLC outputs. The
range can be adjusted from 1 to 120 ms. The output pulse from
inspection functions is timed to pulse at the moment detection is
made. The Total Reject Output pulse occurs when the rejector is
fired. The Total Throughput pulse occurs when the container
passes through the inspection trigger.
See Chapter 9: Using a PLC With Your FT-70 for more information.