EVO S - Installation and Servicing
F. CONFIGURATION OPTIMISATION
Cascade optimisation:
The cascade can be optimised if necessary using the settings in the Cascade menu. Refer to the
NAVISTEM B3000 boiler's controller manual for more details.
Maintenance optimisation
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
• Operating hours of the burner (parameter 7040).
• Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.