EVO S - Installation and Servicing
G. CONFIGURATION OPTIMISATION
DHW optimisation:
• DHW tank menu
Adjust the over value
Maintenance optimisation
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
• Operating hours of the burner (parameter 7040).
• Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
78 / 136
Diagram: VF22
Line No.
Flow setpoint boost (5020)
00RNO0333-B (U0625869)
page 5 / 5
Value
16 °C