• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Configure the cascade cylinder outlet sensor
B10
For a request via 0...10V input
Configure the H1 input
For a request via LPB
Check that the secondary regulatory is defined on an LPB segment other
than 0 (reserved for the generators)
In all cases (LPB network menu)
Configure the boiler as master the of the
cascade:
To display the faults from other modules on
the console of the module you are adjusting
If you want an alarm report on this module
(output K10 (QX1)) containing all the faults
from all the modules
Save the sensors
27.08.2018
Diagram : VF10
EVO S - Installation and Servicing
Line No.
Hours / minutes (1)
Day / month (2)
Year (3)
Sensor input BX2 (5931)
Function input H1 (5950)
Voltage value 1 H1 (5953)
Function value 1 H1 (5954)
Voltage value 2 H1 (5955)
Function value 2 H1 (5956)
Device address (6600)
Segment address (6601)
Bus power supply function
Clock mode (6640)
Display system messages
Syst messages alarm relay
Save sensors (6200)
page 4 / 7
Value
HH.MM
DD.MM
YYYY
Common flow sensor
B10
Consumer request
VK1 10V
0.0
0
10.0
1000 (for equivalence
10 V = 100 °C)
1
0
Automatically
(6604)
Master (or slave with
remote setting if the
PLC is the master
clock)
Yes
(6610)
Yes
(6611)
Yes (switches back to
no automatically)