9.4. Specific configurations when connecting to 0-10V outputs (Ux)

9.4.1.
Controlling a Q1 boiler pump
D. SPECIFIC START-UP PROCEDURE
• Configuration menu
Declare the boiler pump Q1 on the output
chosen.
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
• Boiler menu
Set these 3 parameters to the same value
9.4.2.
Controlling a Q2, Q6 or Q20 heating circuit pump
D. SPECIFIC START-UP PROCEDURE
• Configuration menu
Case of a 0-10V command Q2, Q6 or
Q20 heating pump. Configure the heating
pump.
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
• Heating circuit 1/2/3 menu
Set these 3 parameters to the same value
104 / 136
Line No.
Function output Ux (6078/6089)
Signal logil output UX (6079/6090)
Starting speed (2321)
Pump speed min (2322)
Pump speed max (2323)
Line No.
Function output Ux (6078/6089)
Signal logil output UX (6079/6090)
Starting speed (881/1181/1481)
Pump speed min (882/1182/1482)
Pump speed max (883/1183/1483)
00RNO0333-B (U0625869)
Value
Boiler pump Q1
Standard
between 0 and 100 %
between 0 and 100 %
between 0 and 100 %
Value
Heat circuit pump
HC1 Q2
Or
Heat circuit pump
HC2 Q6
Or
Heat circuit pump
HC3 Q20
Standard
between 0 and 100 %
between 0 and 100 %
between 0 and 100 %