E. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Make the following settings:
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Configure the alarm output
For the DHW to be effective, an
activator must be defined, even if it is
not connected
Configure the tank charge pump
• Consumer circuit 1 menu
Set the output setting to be taken into
account if the Consumer circuit is
requested
Remove pump stoppage on DHW
priority (OEM setting)
• Domestic hot water menu
Adjust the comfort setting
Adjust the DHW release mode
• DWH tank Menu
Adjust the over value
Settings on the Rubis
Adjust the outlet temperature set point on the Rubis to 58°C.
Summary of the rules for the adjustment of the set points for the DHW
Set point of the consuming circuit (low limit) = set point of the outlet T° of the Rubis +5°C
Set point of the DHW on the boiler = set point of the outlet T° of the Rubis +3°C
Over-value of the boiler outlet temperature when the DHW is restarted = 7°C
27.08.2018
Diagram: VF23
Flow temp setp cons request
EVO S - Installation and Servicing
Line No.
Hours / minutes (1)
Day / month (2)
Year (3)
Relay output QX1 (5890)
Relay output QX2 (5891)
Relay output QX3 (5892)
(1859)
DHW priority (1874)
Nominal setpoint (1610)
Release (1620)
Flow setpoint boost (5020)
page 3 / 5
Value
HH.MM
JJ.MM
AAAA
Alarm output K10
DHW ctrl elem Q3
Consumer circuit
pump 1 Q15
60 °C (depends on
the Rubis setting)
No
55 °C
24/day
7 °C
81 / 136