EVO S - Installation and Servicing

5. FIRST USE

5.1. Checks before first use

WARNING:
IMPORTANT:
5.2. First use
IMPORTANT:
36 / 136
Check that the cold pressure is a minimum of 1 bar.
If this is a boiler house renovation, ensure that flushing and if necessary
silt removal from the installation have been correctly done (see chapter
1.5, page 6 of this manual).
Verify the connecting of the gases according to the type of chimney.
Check that the pressure and the type of gas are adapted to the product.
The use of glycol water if forbidden.
The use of the connection accessories is mandatory to connect a
EVO S boiler to a B23 or B23P chimney duct.
Before packing all boilers are subjected to a factory test using group H (type
G20) natural gas during which all the settings are done.
For first use perform the following operations:
1. Switch on the main circuit breaker.
2. Create a request for heat via the comfort mode using the customer
interface (see the chapter "3 - Interface utilisateur" in the NAVISTEM
B3000 boiler controller manual).
3. After starting the burner, check the gas tightness of the gas line connections
using a foaming product. Check combustion health using an exhaust gas
analyser.
4. Adjust the boiler setting (refer to the table summarising customer
parameters at the end of this manual).
Any work on a sealed component will lead to loss of the guarantee.
00RNO0333-B (U0625869)