E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Pump with 0-10 V control
9.4.3.
Controlling a DHW pump Q3
D. SPECIFIC START-UP PROCEDURE
• Configuration menu
Case of a 0-10V command DHW pump.
Configure the DHW pump Q3.
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
• DHW storage tank menu
Set these 3 parameters to the same value
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Pump with 0-10 V control
27.08.2018
EVO S - Installation and Servicing
Line No.
Output test Ux (7716/7724)
Line No.
Function output Ux (6078/6089)
Signal logil output UX (6079/6090)
Pump speed min (5101)
Pump speed max (5102)
Starting speed charg pump (5108)
Line No.
Output test Ux (7716/7724)
Value
in % (1% = 0,1 V)
Value
Pompe ECS Q3
Standard
between 0 and 100 %
between 0 and 100 %
between 0 and 100 %
Value
in V (1% = 0,1 V)
105 / 136