EVO S - Installation and Servicing
E. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Make the following settings:
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Configure the alarm output
Configure the tank pump
Define a low limit
Position a shunt on H1 OU reverse the
contact direction
For the DHW to be effective, an
activator must be defined, even if it is
not connected
• Consumer circuit 1 menu
Set the output setting to be taken into
account if the Consumer circuit is
requested
Remove pump stoppage on DHW
priority (OEM setting)
• Domestic hot water menu
Adjust the comfort setting
Adjust the DHW release mode
Remove the DHW priority
• DHW tank menu
Adjust the over value
76 / 136
Diagram: VF22
Flow temp setp cons request (1859)
Line No.
Hours / minutes (1)
Day / month (2)
Year (3)
Relay output QX1 (5890)
Relay output QX3 (5892)
Function input H1 (5950)
Contact type (5951)
Relay output QX2 (5891)
DHW priority (1874)
Nominal setpoint (1610)
Release (1620)
Charging priority (1630)
Flow setpoint boost (5020)
00RNO0333-B (U0625869)
page 3 / 5
Value
HH.MM
DD.MM
YYYY
Alarm output K10
Consumer circuit
pump 1 Q15
Consumer request
VK1
Normally-closed
contact (NC)
DHW ctrl elem Q3
60 °C (depends on
the Rubis setting)
No
3°C less than the
Rubis set point
24h/day
Without
13 °C