EVO S - Installation and Servicing
Process description
The consuming circuit keeps the temperature of the tank at 63°C. In this case, the set point of the
boiler = the set point of the consuming circuit (63°C).
If the sensor inside the tank detects a temperature = the set point of the DHW (61°C) -5°C, the
DHW cycle starts. The output temperature of the boiler is then = the set point of the DHW (61°C)
+ over-value (7°C) = 68°C.
The DHW cycle stops when the sensor inside the tank reaches the DHW set point temperature
(61°C). The boiler then returns to the set point of the consuming circuit (63°).
• Activate the DHW mode
• Configuration menu
Save the sensors
F. ELECTRICAL AND HYDRAULIC VALIDATION
• Inputs/outputs test menu
Check the outputs
Alarm relay
Tank pump Q15
Reset the outputs
Check the sensor values
B3 DHW sensor
• Configuration menu
Check the hydraulic diagram
82 / 136
Diagram: VF23
Check no. heat source 1 (6212)
Check no. heat source 2 (6213)
Check no. storage tank (6215)
Check no. heating circuits (6217)
Line No.
Save sensors (6200)
Relay test (7700)
Relay test (7700)
Relay test (7700)
DHW temp B3/B38 (7750)