Settings on the Rubis
Adjust the outlet temperature set point on the Rubis to 58°C.
Summary of the rules for the adjustment of the set points for the DHW
Set point of the consuming circuit (low limit) = set point of the outlet T° of the Rubis +5°C
Set point of the DHW on the boiler = set point of the outlet T° of the Rubis -2°C
Over-value of the boiler outlet temperature when the DHW is restarted = 13°C
Process description
The consuming circuit keeps the temperature of the tank at 63°C. In this case, the set point of the
boiler = the set point of the consuming circuit (63°C).
If the sensor inside the tank detects a temperature = the set point of the DHW (56°C) -5°C=51°C,
the DHW cycle starts. The output temperature of the boiler is then = the set point of the DHW
(56°C) + over-value (13°C) = 69°C.
The DHW cycle stops when the sensor inside the tank reaches the DHW set point temperature
(56°C). The boiler then returns to the set point of the consuming circuit (63°).
• Activate the DHW mode
• Configuration menu
Save the sensors
F. ELECTRICAL AND HYDRAULIC VALIDATION
• Inputs/outputs test menu
Check the outputs
Alarm relay
Tank pump Q15
Reset the outputs
Check the sensor values
B3 DHW sensor
Check the status of contact H1
• Configuration menu
Check the hydraulic diagram
27.08.2018
Diagram: VF22
Check no. heat source 1 (6212)
Check no. heat source 2 (6213)
Check no. storage tank (6215)
Check no. heating circuits (6217)
EVO S - Installation and Servicing
Line No.
Save sensors (6200)
Relay test (7700)
Relay test (7700)
Relay test (7700)
DHW temp B3/B38 (7750)
Contact state H1 (7841)
page 4 / 5
Value
Yes (switches back
to no automatically)
Relay output QX1
Relay output QX3
No test
in °C
Closed if the shunt
is in place
13
0
4
0