CHAPTER 12 - OUTDOOR RESET CONTROL

The use of the outdoor reset function is required to op-
timize boiler efficiency, see notice below. If the outdoor
sensor is not installed before turning on the PRESTIGE
Excellence, an Outdoor Sensor Open error (E96) will be
displayed. The error will not prevent the boiler from
operating. The error will automatically reset once the
outdoor sensor is installed or if the outdoor reset func-
tion is disabled. Reference Section 9.7 on page 42
for information on disabling the outdoor reset function.
The outdoor reset function can only be disabled if the
installation meets one of the exceptions listed in the
IMPORTANT notice below.

12.1. Mounting the Outdoor Sensor

1. The exterior wall selected for mounting the out-
door sensor should represent the heat load of the
building. Typically a northern wall will suit most
buildings.
2. Ensure the outdoor sensor is shielded from direct
sunlight or the effects of heat or cold from other
sources (exhaust fans, appliance vents...) to prevent
false temperature readings.
3. Mount the outdoor sensor at an elevation on the
exterior wall to prevent accidental damage or tam-
pering.
4. Avoid mounting the outdoor sensor in areas sub-
jected to excessive moisture.
5. Once an area on the exterior wall has been deter-
mined, follow the mounting instructions included
with the outdoor sensor.
In accordance with Chapter 325 (f ) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a
feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature
is equipped with an override which is provided primarily to permit the use of an external energy management
system that serves the same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS
An external energy management system is installed that reduces the boiler water temperature
as the heating load decreases.
This boiler is not used for any space heating
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/
hr or greater.
This boiler is equipped with a tankless coil.

12.2. Wiring the Sensor

1. Connect 18 AWG 2-wire cable or similar to the out-
door sensor.
2. Route the cable back to the PRESTIGE Excellence
boiler, ensuring the wires are not run parallel to
telephone or power wiring.
If the sensor wires are located in an area
with sources of electromagnetic interference
(EMI), the sensor wires should be shielded or
the wires should be run in a grounded metal
conduit. If using shielded cable, the shielding
should be connected to the common ground of
3. Connect the outdoor sensor wires to low voltage ter-
minals X6-1&2 located at the bottom of the ACVMax
control module as shown in Fig. 18 on page 32.
IMPORTANT
IS TRUE.
NOTICE
the unit.