CHAPTER 8 - EXTERNAL WIRING

8.13. Cascade Wiring

The ACVMax control includes the ability to operate up
to six Prestige Solo boilers together as one without the
need for external controllers. Consult the PRESTIGE
ACVMax Control Supplement for more information.

8.14. Modbus Wiring

The ACVMax control includes the ability to communi-
cate with building management systems (BMS) through
a Modbus interface. Consult the PRESTIGE ACVMax
Control Supplement for more information.
Heat Call
CH1
CH2
DHW
Low Voltage Terminals
CH2
System
Modulation
Thermostat
Sensor
Signal
-
+
6
5
4
3
2
X5
34
PRESET PUMP CONFIGURATION 2
Pump 4
OFF
ON
OFF
External Limit
Terminals
Manual
CH1
Outdoor
DHW
Modbus
CH2
Thermostat
Sensor
Sensor or
Thermosta
Aquastat
+
G
-
t
1
4
3
2
1
2
1
3
2
1
X6
X4
X7
PLUG-IN
CARDS
1
2
3
4
POWER
CONTROLS
SLAVE
EXPANSION
MODE
MASTER
RESET
NORMAL
ZONE 1
N/O
COM
N/C
ENDSW
ENDSW
1
2
3
4
B
A
ZONE 4 RELAY
PUMP
BOILER
1
2
3
4
Zone 1
Zone Valve
System
Circulator

Fig. 19 - Typical Zone Panel Wiring to PRESTIGE with Zone Valves

Modbus communication will only occur if the external
device is properly wired to the PRESTIGE Excellence as
follows:
X7-1 = RS-485 –
X7-2 = RS-485 Ground
X7-3 = RS-485 +
ACV-Triangle Tube has building management sys-
tem (BMS) gateways available to convert Modbus
to most BMS protocols including BACnet® MS/TP,
BACnet® /IP, Metasys® N2, and LonWorks®. Con-
tact ACV-Triangle Tube for more information
Pump 3
DHW Pump
ON
OFF
OFF
Mix Sensor
Line Voltage Terminals
Terminals
Auto
L G N
L G N
L G N
FLAME
PUMP 4
PUMP 3
Zone 1
Zone 2
Zone 3
Thermostat
Thermostat
Thermostat
68
68
68
T
T
T
T
T
T
ZONE 1
ZONE 2
ZONE 3
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
ZONE 2
ZONE 3
ZONE 4
1
2
3
4
1
2
3
4
1
2
1
1
2
2
3
3
4
4
Zone 2
Zone 3
Zone Valve
Zone Valve
NOTICE
CH Pump
ON
ON
ON
ON
OFF
ON
L G N
L G N
L G N
L G N
CH PUMP
ALARM
DHW PUMP
POWER SUPPLY
Internal
120V/15A
Circulator
Service
ZONE 4
PRIORITY
T
T
ON
ZONE 4
OFF
3
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents