CHAPTER 11 - START-UP PROCEDURES
Table 3 - Throttle Screw Adjustment
Direction
Clockwise
Counter-Clockwise

11.3.6 Measure Input - Natural Gas Only

1. Ensure the boiler is firing at maximum firing rate. To
manually place the boiler into high fire, reference
Section 11.3.5 on page 56.
2. Operate the unit for approximately 10 minutes.
3. Turn off all gas appliances within the building, ex-
cept the PRESTIGE Excellence.
4. At the gas meter, record the time required to use
one cubic foot of gas.
5. Calculate Natural gas input using the following
equation:
3600 x 1000 / number of seconds recorded for one
cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate the in-
put rating listed on the unit.

11.3.7 Test High Temperature Limit

The high temperature limit can be temporarily lowered
from 210ºF [99ºC] to 102ºF [39ºC] for testing.
1. Press the round INSTALLER button. Reference Fig.
21 on page 37.
2. Enter the installer access code "054" by using the
LEFT and RIGHT buttons to select a digit and the
UP and DOWN buttons to change the digit. Press
the OK button to enter the access code.
CO 2 Range
CO 2 Target
O 2 Range
O 2 Target
CO 2 Range
O 2 Range
CO Max
Prestige Excellence 110
Increase CO 2
Decrease O 2
Decrease CO 2
Increase O 2
Table 4 - Acceptable Combustion Levels
Natural Gas
8.8 to 10.5%
9.2%
2.3 to 5.3%
4.6%
0.5 to 0.6% Lower than High Fire CO2
0.8 to 0.9% Higher than High Fire O2
100 ppm
3. Press the OK button while CH & DHW Settings icon
is highlighted.
4. Press the DOWN button to highlight the Boiler Set-
then press the OK button.
tings icon
5. Press the DOWN button to highlight Lockout Tem-
perature then press the OK button.
6. Press the UP button to highlight 102ºF [39ºC] then
press the OK button.
7. Press the DOWN button to highlight the Home
then press the OK button.
Screen icon
8. Initiate a CH or DHW call and confirm that a High
Boiler Temperature lockout occurs once the supply
temperature reaches 102ºF [39ºC].
9. Press any ARROW button to return to the Home
Screen.
10. Press the round INSTALLER button.
11. Press the OK button while the CH & DHW Settings
icon
is highlighted.
12. Press the DOWN button to highlight the Boiler Set-
then press the OK button.
tings icon
13. Press the DOWN button to highlight Lockout Tem-
perature, then press the OK button.
14. Press the DOWN button to highlight 210ºF [99ºC]
then press the OK button.
15. Press the DOWN button to highlight the Home
then press the OK button.
Screen icon
16. Press the OK button to reset the lockout and return
the unit to service.
Propane
10.7 to 12.0%
11.0%
2.7 to 4.7%
4.2%
150 ppm
57