CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.3.

Boiler Freeze Protection Feature

The ACVMax boiler management system has a freeze
protection feature built in. This feature monitors the
boiler water temperature and responds as follows
when no call for heat is present:
46ºF [8ºC] Pump outputs configured to respond to
a CH1 Call are enabled.
42ºF [6ºC] Pump outputs configured to respond to
a CH1 or CH2 Call are enabled, Burner operates at
low fire.
60ºF [15ºC] Freeze protection ends. Burner & all
pumps turn off after completing CH Post Pump Time.
CAUTION
The boiler freeze protection feature is dis-
abled during a hard lockout. The burner
will not fire, but the circulators will operate.
The boiler freeze protection feature is de-
signed to protect the boiler, not the heating
system. The boiler should be installed in a
primary/secondary piping arrangement if it
is installed in an unheated space or exposed
to water temperatures of 46ºF or less. Refer
to Chapter 4 for primary/secondary and
Chapter 10 for antifreeze guides.
Failure to comply can result in minor prop-
erty damage, or injury.
1.4.

Boiler Replacement

If the PRESTIGE Excellence is replacing an existing boil-
er, the following items should be checked and correct-
ed prior to installation:
Boiler piping leaks and corrosion.
Proper location and sizing of the expansion
tank on the boiler heating loop.
The existing vent system is appropriate for the
PRESTIGE Excellence and it is correctly installed.
Refer to the PRESTIGE Vent Supplement for the
vent system requirements.
Amount and quality of propylene glycol within
the system, if applicable.
1.5.

Recommended Clearances

The PRESTIGE Excellence is approved for zero clearance
to combustibles, excluding vent and boiler piping.
Boiler piping must be a minimum 1/4 inch from
combustible materials.
2
Reference the PRESTIGE Vent Supplement for
vent pipe clearance requirements.
BEST PRACTICE
It is recommended that the following clearances
be maintained for serviceability:
Top boiler jacket - 24 inches [610 mm].
Front - 24 inches [610 mm].
Bottom boiler piping - 24 inches [610 mm].
Rear - 0 inches
Sides - 6 inches [153 mm]
NOTICE
When maintaining less than recommended
service clearances, some product labeling, in-
cluding the rating label, may become hidden
and unreadable.
WARNING
If the recommended clearances list-
ed
above
cannot
or the enclosure in which the boil-
er is installed is less than 85 cubic
feet, the space must be ventilated.
See Section 2.2 on page 4.
When installing the PRESTIGE Excellence
in a confined space, sufficient air must be
provided to allow, under normal operat-
ing conditions, proper air flow around the
product to maintain ambient tempera-
tures within safe limits to comply with the
National Fuel Gas Code (NFPA 54 / ANSI
Z223.1)
Failure to comply with these instructions
can result in substantial property dam-
age, serious injury, or death.
1.6.

Residential Garage Installations

When installing the PRESTIGE Excellence in a residen-
tial garage, the following special precautions per NFPA
54/ANSI Z223.1 must be taken:
Mount the unit a minimum 18 inches [458 mm]
above the floor level of the garage. Ensure the
burner and ignition devices / controls are no less
than 18 inches [458 mm] above the floor level.
Locate or protect the unit in a manner so it can-
not be damaged by a moving vehicle.
be
maintained