CHAPTER 7 - INTERNAL WIRING

WARNING
ELECTRICAL SHOCK HAZARD. For your safe-
ty, disconnect electrical power supply to the
unit before servicing or making any electrical
connections to avoid possible electric shock
hazard. Failure to do so can cause serious in-
jury, or death.
CAUTION
Prior to servicing, label all wires before discon-
necting. Wiring errors can cause improper and
dangerous operation. Verify proper wiring and
operation after servicing.
7.1.

General Requirements

Wiring must be N.E.C Class 1.
If original wiring as supplied with the unit must
be replaced, use only Type T 194ºF [90ºC] wire or
equivalent as a minimum.
The PRESTIGE
Excellence must be electrically
grounded as required by National Electrical Code
(ANSI/NFPA 70) for installations in the U.S., or the
Canadian Electrical Code Part 1(CSA C22.1) for in-
stallations in Canada.
7.2.

Fuse Locations

The ACVMax control module contains 3 internal re-
placeable 5A fuses as shown in Fig. 15 below.
The top two fuses protect the PRESTIGE Excellence
as well as the CH, DHW, and Flame outputs.
The bottom fuse protects the P3, P4, and Alarm
outputs.
Spare fuses are located on the back of the control
module enclosure.
Location
of Fuses

Fig. 15 - ACVMax Control Module Fuse Location

29