CHAPTER 9 - ACVMAX OPERATION
9.7.

Heating EZ Setup

Heating EZ Setup allows the installer to quickly customize the central heating settings for the application.

9.7.1 Select CH Demand (No outdoor sensor connected)

EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
68°F
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
42
CH1 Setpoint
140°F
188°F
CH2 Setpoint
140°F
68°F
188°F
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Select CH Demand prompts the installer to select how a CH De-
mand is generated.
Thermostat & Setpoint - A central heating call from a thermostat
or zone panel will enable the Prestige and the setpoint will be fixed
for central heating calls. After Thermostat & Setpoint is selected, the
CH1 Setpoint screen appears. (see below).
Constant & Setpoint - The Prestige will maintain setpoint without
an external CH call from a thermostat or zone panel. The setpoint
will be fixed for CH calls. After Constant & Setpoint is selected, the
CH1 Setpoint screen appears.
CH1 Setpoint prompts to enter the fixed setpoint for a CH1 heating
call when a Setpoint option is chosen in Select CH Demand.
Press the LEFT or RIGHT buttons to adjust the temperature setpoint
then press OK to store the setting. The CH2 Setpoint screen then
appears.
CH2 Setpoint prompts to enter the fixed setpoint for a CH2 heating
call when a Setpoint option is chosen in Select CH Demand.
Press the LEFT or RIGHT buttons to adjust the temperature setpoint
then press OK to store the setting and complete the Heating EZ Set-
up.
CH1 Default: 140°F [60°C]
CH2 Default: 140°F [60°C]
0 - 10V Modulation Signal - This option allows the Prestige firing
rate to be controlled by an external control system.
Refer to Chapter 13 on page 61 for more information.