Domestic Hot Water Ez Setup - TriangleTube PRESTIGE Excellence 110 Installation & Maintenance Manual

Hide thumbs Also See for PRESTIGE Excellence 110:
Table of Contents

Advertisement

CHAPTER 9 - ACVMAX OPERATION
9.8.

Domestic Hot Water EZ Setup

Domestic Hot Water EZ Setup allows the installer to quickly customize the Domestic Hot Water settings for the application
EZ Setup
DHW EZ Setup
Select DHW Demand
Thermostat
Sensor
96°F
Select DHW Demand
Thermostat
Sensor
DHW Storage Setpoint
68°F
44
DHW
Boiler Setpoint
168°F
188°F
140°F
168°F
DHW Priority Timeout
O
O
120 min.
EZ Setup Complete
DHW EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Select DHW Demand prompts the installer to select how a DHW
Demand is generated.
When Thermostat is selected in Select DHW Demand, a domestic
hot water call from an aquastat or dry contact switch will enable
the Prestige with a fixed setpoint for a domestic hot water call. After
Thermostat is selected, the DHW Boiler Setpoint screen appears.
Default: Sensor
DHW Boiler Setpoint prompts to enter the fixed boiler setpoint
temperature during a domestic hot water call.
Press the LEFT or RIGHT buttons to adjust the temperature set-
point then press OK to store the setting. The DHW Priority Timeout
screen then appears (see below).
Default: 168°F
[76°C].
The PRESTIGE Excellence utilizes an Indirect Water Heater sensor.
When Sensor is selected in Select DHW Demand, use of an Indirect
Water Heater Sensor is required. The Prestige monitors the DHW stor-
age temperature and generates a DHW call whenever the tempera-
ture drops below the DHW storage setpoint by 6°F [3°C].
DHW Storage Setpoint prompts to enter the DHW Storage Set-
point temperature.
Press the LEFT or RIGHT buttons to adjust the temperature setpoint
then press OK to store the setting. The DHW Priority Timeout screen
then appears.
Default: 140°F [60°C].
NOTICE
The DHW Boiler Setpoint will automatically be set 28°F
[15°C] higher than the DHW Storage Setpoint setting
DHW Priority Timeout prompts to enter an optional time limit that
a domestic hot water call has priority over central heating call.
Press the LEFT or RIGHT buttons to adjust the timeout value, if re-
quired, then press OK to store the setting and complete the DHW EZ
Setup.
Defau
lt: Off