CHAPTER 5 - INSTALLING VENT/COMBUSTION AIR & CONDENSATE DRAIN
8. Route the tube from the condensate drain assem-
bly to a floor drain or condensate pump.
NOTICE
When selecting and installing a condensate
pump, ensure the pump is approved for use
with condensing appliances. The pump should
be equipped with an overflow switch to prevent
property damage from potential condensate
spillage.
9. The PRESTIGE Excellence will typically produce a
condensate that is considered slightly acidic with a
pH content below 4.0. Install a neutralizing filter if
required by authority having jurisdiction.
24
Retaining Nut
Metal Washer
Plastic Ball
(Not shown)
Condensate
Drain Assembly

Fig. 12 - Condensate Drain Assembly

WARNING
The condensate drain assembly must remain
filled with water. Extended periods of non
use or high temperature operation may allow
the water to evaporate. Periodically check
the water level in the condensate drain as-
sembly and fill with water as necessary. Fail-
ure to keep the condensate drain assembly
full of water can result in substantial proper-
ty damage, serious injury, or death.
CAUTION
The condensate drain assembly must remain
unobstructed and allow unrestricted flow of
condensate. The condensate should not be
subject to conditions where freezing could oc-
cur. If the condensate is subjected to freezing
or becomes obstructed , it can leak, resulting in
potential water damage to the boiler and sur-
rounding area.
Fill Plug
with Vaccum
Break Port
Compression
Nut with Rubber Seal
Flexible Tubing
(or 3/4 PVC/
CPVC Piping
to Drain)