Addressing Of The Data; Profinet; Profinetio-05 Accessory; Connector - WEG CFW-11 User Manual

Anybus-cc
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

2.4.5

Addressing of the data

Modbus TCP does not define a channel of cyclic data dedicated like in other networks. However, in the Anybus-
CompactCom module, the I/O words can be accessed by the network by means of dedicated registers.
The I/O words can be accessed as bits (Coils and Discrete Inputs) or as registers of 16 bits (Holding Registers
and Input Registers).
The parameters of the drive can be accessed only as holding registers.
The Modbus mapping is presented in the table below:
0000h ... 00FFh
0100h ... 01FFh
0210h ... FFFFh
0000h ... 00FFh
0000h ... 0FFFh
0000h ... 0FFFh
NOTE!
Writings in reading words will have no effect, and the reading of not used registers will return to value
zero.
2.5

PROFINET

2.5.1

PROFINETIO-05 Accessory

Connector

The PROFINET IO communication module has two standard female RJ45 connectors (T-568A or T-568B). It
features integrated switch, enabling the connection in
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 2.17: Addressing for Holding Registers
Address range
Anybus Writing Words
Anybus Reading Words
Parameters of the drive
To find the address of the register corresponding to
the parameter:
ADDR = 210h + (Parameter Number – 1)
Example:
P0003 = 210h + (3h – 1h) = 212h
P0100 = 210h + (64h – 1h) = 273h
Table 2.18: Addressing for Input Registers
Address range
Anybus Reading Words
Table 2.19: Addressing for Coils
Address range
Anybus Writing Words
Table 2.20: Addressing for Discrete Inputs
Bit address range
Reading Words Anybus
WEG part number: 11550548.
Composed by the Anybus ABCC-EIT communication module,
mounting instructions and a "torx" screw driver for fixing the
module.
Two Standard RJ45 connectors.
Description
Description
Description
Description
daisy chain
.