8192 => 1800 rpm
2048 => Speed in rpm
Speed in rpm = 1800 × 2048
8192
Speed in rpm = 450 rpm
Negative values in this parameter indicate that the motor is running in the reverse direction.
P0686 – ANYBUS-CC CONTROL WORD
Range:
0000h to FFFFh
Properties:
-
Access groups
via HMI:
Description:
It is the device Anybus-CC interface control word. This parameter can only be changed via Anybus-CC
interface. For the other sources (HMI, etc.) it behaves like a read-only parameter.
In order to have those commands executed, it is necessary to program the equipment to be controlled via
Anybus-CC. This programming is achieved by means of parameters P0105 and P0220 to P0228.
Each bit of this word represents a command that can be executed.
Bits
Function
Bits
Bit 0
Run/Stop
Bit 1
General enable
Bit 2
Speed direction
Bit 3
JOG
Bit 4
LOC/REM
Bit 5
Second ramp
Bit 6
Quick stop
Bit 7
Fault reset
Bits 8 to 15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
01 PARAMETER GROUPS
49 Communication
111 Status and commands
15 to 8
Table 3.3: P0686 parameter bit functions
1: The motor runs according to the acceleration ramp until reaching the speed reference value.
0: It disables the drive, interrupting the supply for the motor.
0: To run the motor in a direction opposed to the speed reference.
1: To run the motor in the direction indicated by the speed reference.
0: The drive uses the first ramp values, programmed in P0100 and P0101, as the motor acceleration
1: The drive is configured to use the second ramp values, programmed in P0102 and P0103, as the
Note: This function is not allowed with control types (P0202) V/f or VVW.
7
6
5
Values
0: It stops the motor with deceleration ramp.
1: It enables the drive allowing the motor operation.
0: It disables the JOG function.
1: It enables the JOG function.
0: The drive goes to the Local mode.
1: The drive goes to the Remote mode.
and deceleration ramp times.
motor acceleration and deceleration ramp times.
0: It does not execute the quick stop command.
1: It executes the quick stop command.
0: No function.
1: If in a fault condition, then it executes the reset.
Reserved.
Default: 0000h
4
3
2
1
0