Digital and Analog Inputs and Outputs
P0233, P0243
0
1
2
3
When current signals are used at the input, the switch corresponding to the desired input must be set in the "ON"
position.
Inverse reference is obtained with the options 2 and 3, i.e., maximum speed is obtained with minimum reference.

13.1.2 Analog Outputs [39]

In the CFW-11 standard configuration are available 2 analog outputs (AO1 and AO2), and 2 more (AO3 and
AO4) can be added with the IOA-01 accessory. The parameters related to those outputs are described next.
NOTE!
The parameter associated with the AO3 and AO4 analog outputs will be showed on the HMI only
when the IOA-01 module is connected into the Slot 1 (XC41).
P0014 – AO1 Value
P0015 – AO2 Value
Adjustable
Range:
P0016 – AO3 Value
P0017 – AO4 Value
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
Those read only parameters indicate the value of the analog outputs AO1 to AO4, as a percentage of the full
scale. The indicated values are those obtained after the multiplication by the gain. Refer to the description of the
parameters P0251 to P0261.
13
13-6
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 13.2 - Configuration of the analog input signals
P0238, P0248
0
1
2
3
4
0.00 to 100.00 %
-100.00 to 100.00 %
RO
07 I/O CONFIGURATION
39 Analog Outputs
Input Signal
(0 to 10) V / (0 to 20) mA
(4 to 20) mA
(10 to 0) V / (20 to 0) mA
(20 to 4) mA
(-10 to +10) V
or
01 PARAMETER GROUPS
39 Analog Outputs
Switch Position
Off/On
On
Off/On
On
Off
Factory
Setting:
Factory
Setting: