Analog Outputs - WEG CFW700 Programming And Troubleshooting Manual

Hide thumbs Also See for CFW700:
Table of Contents

Advertisement

P0233 – AI1 Signal Type
P0238 – AI2 Signal Type
Adjustable
0 = 0 to 10 V / 20 mA
Range:
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
4 = -10 V to +10 V
Properties:
cfg
Access groups
I/O
via HMI:
Description:
These parameters configure the signal type (if it is current or voltage) that will be read at each analog input, as
well as its range. Refer to the
P0238, P0233
When current signals are used at the input, the switch corresponding to the desired input must be set in the
"ON" position.
Inverse reference is obtained with the options 2 and 3, i.e., maximum speed is obtained with minimum reference.

13.1.2 Analog Outputs

In the CFW700 standard configuration are available 2 analog outputs (AO1 and AO2). The parameters related to
those outputs are described next.
P0014 – AO1 Value
P0015 – AO2 Value
Adjustable
0.00 to 100.00 %
Range:
Properties:
ro
Access groups
I/O or READ
via HMI:
Description:
Those read only parameters indicate the value of the analog outputs AO1 and AO2, as a percentage of the full
scale. The indicated values are those obtained after the multiplication by the gain. Refer to the description of
the parameters P0251 to P0256.
tables 13.1
and
13.2
for more details on this configuration.
Table 13.1: DIP Switches related to the analog inputs
Parameter
Input
P0233
AI1
P0238
AI2
Table 13.2: Configuration of the analog input signals
Input Signal
0
(0 to 10) V / (0 to 20) mA
1
(4 to 20) mA
2
(10 to 0) V / (20 to 0) mA
3
(20 to 4) mA
4
(-10 to +10) V
Digital and Analog Inputs and Outputs
Factory
Setting:
Switch
Location
S1.2
Control Board
S1.1
Switch Position
Off/On
On
Off/On
On
Off
Factory
Setting:
0
13
CFW700 | 13-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents