P0696 - VALUE 1 FOR ANALOG OUTPUTS

P0697 - VALUE 2 FOR ANALOG OUTPUTS

P0698 - VALUE 3 FOR ANALOG OUTPUTS

P0699 - VALUE 4 FOR ANALOG OUTPUTS

Range:
Properties:
Description:
They allow the control of the analog outputs by means of network interfaces (EtherCAT, etc.). It is not possible to
change this parameter via HMI.
The value written in these parameters may control the analog output value, as long as you program the option "P0696
... P0699 value" at the analog output function parameters.
The value must be written in a 15-bit
P0696 = 0000h (0 decimal) → analog output value = 0 %
P0696 = 7FFFh (32767 decimal) → analog output value = 100 %
The showed example was for P0696, but the same scale is also used for the other parameters. For instance, to
control the analog output 1 via EtherCAT, the following programming must be done:
Choose a parameter from P0696 ... P0699 to be the value used by the analog output 1. For this example, we
are going to select P0696.
Program the option "P0696 value" as the function for the analog output 1 in P0254.
Using the network interface, write in P0696 the desired value for the analog output 1, between 0 and 100 %,
according to the parameter scale.
NOTE!
If the analog output is programmed for working from -10 V to 10 V, negative values for this parameter
must be used to command the output with negative voltage values, i.e., -32768 to 32767 represent a
variation from -10 V to 10 V at the analog output.
P0850 – FIRMWARE REVISION FOR ETHERCAT ACCESSORY
Range:
Properties:
Description:
EtherCAT accessory has an internal processor responsible by running the communication routines and perform data
exchange with CFW11 frequency inverter. This parameter identify the firmware revision of this accessory.
1
For the actual output resolution, refer to the product manual.
-32768 ... 32767
RW
1
scale (7FFFh = 32767) to represent 100 % of the output desired value, i.e.:
0 a 65535
ro, ecat
Parameterization
Default: 0
Default: -
CFW11 | 17