Address In The Devicenet Network; Termination Resistors; Cables; Installation Recommendations - WEG CFW-11 User Manual

Anybus-cc
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

All the equipment of the network must be set to use the same communication rate.

Address in the DeviceNet network

Every device in the Anybus-CC network must have an address, or MAC ID, between 0 and 63. This address
must be different for each device.

Termination resistors

The use of termination resistors at the ends of the CAN bus is essential to prevent reflection in the line, which
may damage the signal transmitted and cause errors in the communication. Termination resistors of 121 Ω /
0.25 W must be connected between the signals CAN_H and CAN_L at the ends of the main bus.

Cables

A shielded cable must be used with two pairs of wires, as specified in the DeviceNet protocol.

Installation recommendations

In order to interconnect the network nodes, it is recommended the connection of the equipment directly from
the main line, without the use of derivations. If you use derivations, the limits of length for derivation defined by
the DeviceNet specification must be observed. During the installation of the cables, you must avoid passing
them close to power cables, since that can cause errors during the transmission due to electromagnetic
interference.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 2.5: Communication rates supported and cable length
Communication
Rate
500 Kbit/s
250 Kbit/s
125 Kbit/s
Figure 2.1: Example of installation of the termination resistor
Figure 2.2: Example of installation in DeviceNet network
Length of the
cable
100 m
250 m
500 m

Advertisement

Table of Contents
loading

Table of Contents