Digital and Analog Inputs and Outputs
(
12 – 4
AIx(%) =
16
AIx' = -30.0 % means that the motor will spin counterclockwise with a reference in module equal to 30.0 % of
P0134 if the signal AIx function is "Speed Reference".
In the case of filter parameters (P0235, P0240 and P0245), the value set corresponds to the time constant used to
filter the input signal read. Therefore, the filter response time is around three times the value of this time constant.

12.2 ANALOG OUTPUTS

The analog outputs (AOx) are configured by means of three types of parameters: function, gain and signal, as per
block diagram of
The standard CFW500-IOS plug-in module has just the analog output AO1, but the CFW500-IOAD plug-in provides
one more analog output AO2.
P0014 – Analog Output AO1 Value
P0015 – Analog Output AO2 Value
12
Adjustable
Range:
Properties:
Access Groups
via HMI:
Description:
Those read-only parameters indicate the value of the analog outputs AO1 and AO2 in percentage of the full
scale. The indicated values are those obtained after the multiplication by the gain. Check the description of
parameters P0251 to P0256.
12-6 | CFW500
(
x (100 %) + (-80 %) x 1 = -30.0 %
Figure 12.3 on page
12-6.
Function
AO1 – P0251
AO2 – P0254
P0001
P0002
P0003
P0040
AO1 – P0252
P0011
AO2 – P0255
P0041
P0009
SoftPLC
P0037
P0696
P0697
P0698
(*) Control terminals available in the plug-in module.
Figure 12.3: Block diagram of analog outputs – AOx
0.0 to 100.0 %
ro
READ, I/O
AO1 – P0014
AO2 – P0015
Gain
Signal
AO1 – P0253
AO2 – P0256
Value AOx
AO1(*)
AO2(*)
Factory
Setting: