APPENDICES

Appendix A: Specifications

Table A.1 MPH2 Rack PDU Specifications
Input Power Configurations; vary by model and region
Single-Phase Input; CE-Mark
240 VAC, 16 A; also UL-listed
230 V, 32 A
Three-phase Input; CE-Mark
230/400 V, 16 A
230/400 V, 32 A
Single-Phase Input, UL-Listed
120 VAC, 12A
120 VAC, 16 A
120 VAC, 24 A
208 VAC, 24 A
Three-Phase Input; UL-Listed
120/208 VAC, 24 A
120/208 VAC, 40 A
120/208 VAC, 48 A
240/415 VAC, 24 A
Input Wiring Options
Receptacle Options
Maximum Number of Receptacles
Maximum Power Consumption
Measurement Accuracy
Insulation
Dielectric Electric Strength
Overcurrent Protection
Operating Temperature Range
Storage Temperature Range
Humidity %
Altitude ft (m)
Mounting
Width x Depth Inches (mm)
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide
0U
10-ft (3-m) non-detachable power supply cord.
Hard-wired terminal block for connection of field wiring
NEMA 5-20; IEC 320C13; IEC 320C19
48
Voltage - +/- 1% +0.1 VAC
Current - +/- 1.5% +0.01 A from 1 % to 10 % of unit rating
+/- 1% +0.01 A from >10% to 125% of unit rating
Class I reinforced SELV
Tested up to 4242 VDC
UL489-Listed, CSA, TUV, CCC hydraulic-magnetic circuit breaker, 20 A, 5000 A, A.I.C
32 A or less input models: 41° F to 140° F (5° C to 60° C)
40 A and 48 A input models without case ventilation: 41° F to 122° F (5° C to 50° C)
40 A and 48 A input models with case ventilation: 41° F to 140° F (5° C to 60° C)
-4° F to 185° F (-20° C to 85° C)
10% to 90% non-condensing
6562 ft (2000 m)
Factory-installed tool-less
brackets
Universal mounting bracket
Low-profile: 2.2 x 1.96 (56 x 50)
Standard: 2.2 x 2.7 (56 x 69)
1U
3.8 kW
7.3 kW
11 kW
22 kW
1.4 kW
1.9 kW
2.8 kW
4.9 kW
8.6 kW
14.4 kW
17.2 kW
12
6 W
Factory installed, right-angle mounting brackets
1.73 x 9.84 (44 x 250)
2U
24
3.46 x 9.84 (88 x 250)
39