Mounting A Horizontal Mph2™ Rack Pdu On Vertical Frame Member With Aluminum Extrusions - Vertiv MPH2 Installer/User Manual

Rack pdu
Hide thumbs Also See for MPH2:
Table of Contents

Advertisement

2. Hold the MPH2™ Rack PDU over the desired mounting holes (now with the cage nuts), and
route the input cable through the rack as desired.
3. Insert screws and use a Torx T30 screwdriver to tighten all of them. Leave the screws slightly
loose for the time being,
4. Once all the screws are installed, tighten using a torque setting of 4 Nm or 35.4 lb-in.
Figure 3.6 Installing horizontal MPH2™ Rack PDU in a rack
3.3.4 Mounting a Horizontal MPH2™ Rack PDU on Vertical Frame Member with Aluminum
Extrusions
1.
Choose a position in the rack for the PDU and install four spring nuts into the groove.
2. Use a level to check if the horizontal plane is maintained.
3. Set the distance to match the holes on the PDU, and hold the MPH2™ Rack PDU over the
desired position (now with the spring nuts).
4. Route the input cable through the rack as desired.
5. Insert screws and use a Torx T30 screwdriver to tighten all of them. Leave the screws slightly
loose for the time being.
6. Once all the screws are installed, tighten using a torque setting of 44.3 lb-in (5 Nm).
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide