Figure 3.7 Installing horizontal MPH2™ Rack PDU in a rack with aluminum extrusions

3.3.5 Rack Grounding strap

NOTE: Ensure that the safety-earth connection at the input-power-source receptacle is electrically
connected before any equipment is connected to Vertiv™'s MPH2™ Rack PDU.
Units with factory-attached input-power cords have a grounding conductor internal to the case. The rack
grounding strap establishes the same ground potential between the MPH2™ Rack PDU and the rack
enclosure.
NOTE: The grounding strap may be used with rack PDUs that have attached input-power cords and
units that have hard-wired input-power cords. The strap supplements the internal grounding
conductor of the attached power-supply cord.
NOTE: When connecting multiple Class 1 devices, the ground leakage currents may be significant. The
additional external ground connection helps reduce ground impedance between the MPH2 PDU and
the rack enclosure. The rack-grounding strap may be ordered as an option.
The grounding strap may be particularly useful when the rack is on a raised floor.
Table 3.3
Ground-strap wire gauge by
RATING
12 A
16 A
24 A
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide
rating
MPH2™ Rack PDU
WIRE SIZE
UL LISTED
CE MARKED
14 AWG
4.0 mm
12 AWG
10 AWG
WORLD-WIDE (WW)
2
12 AWG or 4.0 mm
2
19