For mounting a vertical MPH2™ Rack PDU: 
Phillips #2 screwdriver
For mounting a horizontal MPH2™ Rack PDU: 
Flat-blade screwdriver
Torx screwdriver TX30
Torque wrench
Level
3.3.2 Mounting the Vertical MPH2™ Rack PDU
The vertical MPH2™ Rack PDU can be installed on a vertical or horizontal frame member in the rack.
1.
Determine where in the rack the PDU will be installed.
2. Attach a bracket to each end of the PDU.
3. If mounting on horizontal frame members, attach the brackets in-line,
- or -
If mounting on a vertical frame member, attach the brackets at a right angle to the PDU.
4. Insert two spring nuts into the appropriate T-slot on the frame member. Position the spring
nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts,
press down on each with a small, pointed object and slide each into position.
5. Hold the PDU in place and attach the top of the unit to the rack with tool-less fasteners.
6. Tighten the screws, using a torque setting of 46 lb-in (5.2 Nm).
7. Repeat steps 4-6 for the lower bracket on the lower end of the PDU.
Figure 3.5 Installing vertical MPH2™ Rack PDU in a rack
3.3.3 Mounting the Horizontal MPH2™ Rack PDU
The horizontal MPH2™ Rack PDU is installed on a vertical frame member in the rack.
1.
Choose a position in the rack for the PDU and install four cage nuts into the respective slots.
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide
17