Table 4.1 Factory-default settings
LEVEL
SETTINGS
User Assigned Label
Asset Tag 1
Asset Tag 2
Overcurrent Alarm
Threshold
PDU
Overcurrent Warning
Threshold
Undercurrent Alarm
Threshold
Unbalanced Load Alarm
threshold
Software Over Current
Protection (SWOCP)
User Assigned Label
Asset Tag 1
Asset Tag 2
Overcurrent Alarm
Threshold
Branch
Overcurrent Warning
Threshold
Undercurrent Alarm
Threshold
SWOCP
User Assigned Label
Asset Tag 1
Asset Tag 2
Overcurrent Alarm
Threshold
Overcurrent Warning
Threshold
Undercurrent Alarm
Threshold
Power Up State
Receptacle
Power On Delay
Power Cycle Delay
Post On Delay
Post Off Delay
Software Over Temperature
Protection (SWOTP)
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide
DEFAULT
MODELS
UNITS
VALUE
AFFECTED
MPH2™
Rack PDU
or
All
Rack PDU
<alpha>
<empty>
All
<empty>
All
45
%
All
40
%
All
0
%
All
0
%
All 3-phase
Disabled
R
Branch
All
<alpha>
<empty>
All
<empty>
All
95
%
All
90
%
All
0
%
All
Disabled
R
Receptacle
All
<number>
<empty>
All
<empty>
All
95
%
M,R
90
%
M,R
0
%
M,R
Restore
C,R
0
seconds
C,R
8
seconds
C,R
0
seconds
C,R
0
seconds
C,R
Disabled
C,R
NOTES
RackPDU is default value the first time only.
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
% calculated from maximum input-current rating on
nameplate.
Default values are recommended for dual-corded server
applications.
% difference calculated between any two phases.
Conditionally applies to unlocked and unloaded receptacles
only.
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
% calculated from CB rating. Refer to nameplate for
maximum branch current rating.
Conditionally applies to all unlocked and unloaded
receptacles only for this branch.
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Configurable per receptacle.
% calculated from maximum receptacle current rating on
nameplate.
Restore returns receptacle power state to last
programmed state after expiration of Power On Delay.
The delay timing begins after measurement stability is
achieved.
A Power Cycle turns off power to the receptacle for the
specified delay.
Delay before RPC2 issues command to power on
receptacle.
Delay before RPC2 issues command to power off
receptacle.
Unconditionally applies regardless of locked/unlocked and
loaded/unloaded status.
At least one temperature sensor is required.