Table B.2 Line LED Troubleshooting
LED INDICATION
(ONE OR ALL LEDS)
STATE/
COLOR
FLASH
SPEED
Green
Steady On
Off
NA
Red
Steady On
Red
Fast
Green
Slow
Green/Red
Fast
Vertiv | Vertiv™ MPH2 Rack PDU Installer/User Guide
AUDIBLE
CONDITION
STATUS/RECOMMENDED ACTION
ALARM
Normal Operation
None
Note: Depending on plug type, not all LEDs may be lit, see
Plug Type
Confirm that the LED is active per
Voltage Off
Check power source and input plug's receptacle wiring.
Check receptacle power control settings.
Check power source for power quality problem. If the MPH2™ Rack PDU uses 3-phase
Line
power, a single low-voltage phase may cause one or more undervoltage alarms. The
ü
Undervoltage
undervoltage alarm is factory-set to -10% of the minimum input voltage range on the
Alarm
nameplate; it cannot be changed.
Check for changing load conditions.
Overcurrent
Alarm
Check overcurrent alarm threshold settings.
ü
Check for removal of load.
Undercurrent
Alarm
Check undercurrent alarm threshold settings.
Check for changing load conditions.
Overcurrent
Warning
Check overcurrent warning threshold settings.
Firmware
Firmware update in-progress. LCD does not display information. If the update fails or
Update
aborts, the indication continues until firmware update is tried again and is successful.
on page 43.
Additional Troubleshooting by Plug Type
Additional Troubleshooting by
on page 43.