Buzzer, Backlight, and Display Control
[Operation]
Sounding the Buzzer by the Operation at the Status Control Area
[Setting]
[Operation]
15
14
13
12
11
10
9
0
470
When the screen where the buzzer attribute has been set is displayed during the
operation of the NT31/NT31C, the buzzer sounds automatically according to the
setting. For the procedure for changing the screen, refer to 8-3-1 "Switching the
Screen" (page 480).
This method allows the operator to sound the buzzer at any required time.
Buzzer sounds
The PT status control area must be allocated to a word in the host and, according-
ly, there are no special settings required for the control of buzzer.
The bit for controlling the PT status (PT status control bit) is provided at the fourth
word (n + 3 words) from the beginning of the PT status control area.
8
7
6
5
4
3
2
NT31/NT31C
1
0
Bit
0
Controlled Item
Screen display
15
14
Processing priority registration (for NT link (1:N))
13
Continuous buzzer
12
Intermittent buzzer (short)
11
Display history initialization
10
Not used
9
Intermittent buzzer (long)
Backlight mode
8
7
Screen printing
6
PT window opening
5
Numeral/character string input
4
PT screen switching
3
Memory table copy execution
Memory table copy type
2
Alarm history initialization
1
Not used
0
Section 8-2
PC
PT status control area
Screen switch setting
Copy memory
table setting
← Control data
PT status control setting
Reserved for system use
1 (ON)
Performed
Not performed
Registered
Canceled
Sounded
Sounded
Performed
Not performed
Always "0"
Sounded
Lit
Performed
Not performed
Disabled
Disabled
Disabled
Performed
Not performed
Numeral
Character string
Performed
Not performed
Always "0"
0 (OFF)
Stopped
Stopped
Stopped
Flashing
Enabled
Enabled
Enabled