Connecting to the Host's RS-232C Port
5-1-2
1:1 Connection between RS-422A/485 at the NT31/NT31C and
RS-232C at the Host
Reference: When using RS-485 as a port for the NT31/NT31C, only NT link (1:N) method can
Connecting an NT31/NT31C and NT-AL001 (RS-422A)
The connection method in which the RS-422A/485 port of an NT31/NT31C and
the RS-232C port of a host are connected via a convertor unit is described here.
An RS-232C/RS-422A convertor unit (NT-AL001) is used to convert between the
RS-232C and RS-422A communication methods.
NT31/NT31C
25-pin connector
be used.
NT31/NT31C
1
14
13
25
In order to avoid an FG ground loop, do not make the connection between the func-
tional ground of the NT-AL001 and the shielding.
Serial port B
(RS-422A/485,
25-pin type)
RS-232C/RS-422A
convertor unit
(NT-AL001)
RS-422A/485 cable
(max. length: 500 m)
RS-422A terminal block
NT-AL001
RS-422A
NT31/NT31C side
Abbreviation
Pin number
Shielding wire
Connector
FG
hood
1
SD
2
RS-232C/
422A/485
RD
3
connector
RS
4
CS
5
6
SG
7
8
TRM
9
RDB (+)
10
SDB (+)
11
12
13
14
SDA (−)
15
16
RDA (−)
RSB (+)
23
RSA (−)
24
25
(25-pin type)
Section 5-1
Host link unit/CPU
SYSMAC
C-series PC,
CVM1/CV-series PC, SRM1
9-pin connector or
25-pin connector
RS-232C cable
with connectors
9-pin connector
Host
NT-AL001 side
Pin number
Abbreviation
6
RDA
5
RDB
RS-422A
terminal
4
SDA
block
3
SDB
Functional
1
ground
8
7
6
5
4
3
2
1