GE Multilin 565 Instruction Manual page 72

Feeder management relay
Table of Contents

Advertisement

SETPOINTS MODE - CONFIGURATION
Location
Message Line
CONDITION
NO ALARM
ALARM
(Alarm Level < Curr. < P/U)
(Brkr. Open)
ALARM
(Curr. > Alarm & P/U Level)
ALARM
(Curr. < Alarm & P/U Level)
(Brkr. Open)
KEYPAD RESET
CONDITION
NO TRIP
TRIPPED
(Current > Trip Level)
TRIPPED
(Current < Trip Level)
KEYPAD RESET
CONDITION
NO ALARM
ALARM
(Current > Alarm Level)
ALARM
(Current < Alarm Level)
KEYPAD RESET
5-28
Description
OUTPUT
AUX. 1 RELAY
DE-ENERGIZED
PULSES
ENERGIZED
DE-ENERGIZED
DE-ENERGIZED
Latched
If latched operation is chosen for the Aux 1 relay, it will energize when a
trip/alarm occurs. Pressing the RESET key on the front panel will unlatch
the Aux 1 relay only if the fault current is below the trip/alarm level. This
may be convenient if the relay is being used to annunciate a fault condition.
When programmed as latched, the Aux 1 relay does not look at the 52a/
52b contacts.
OUTPUT AUX. 1
RELAY
DE-ENERGIZED
ENERGIZED
ENERGIZED
DE-ENERGIZED
OUTPUT AUX. 1
RELAY
DE-ENERGIZED
ENERGIZED
ENERGIZED
DE-ENERGIZED
Unlatched
If unlatched operation is selected, the Aux 1 relay becomes energized
upon declaration of a fault/ alarm condition. When current drops below the
alarm/trip level, the relay will de-energize. When programmed as un-
latched, the Aux 1 relay does not look at the 52a/52b contacts.
FACEPLATE
MODBUS READ EXCEPTION
AUX. 1 LED
OFF
ON
OFF
OFF
OFF
FACEPLATE
MODBUS READ EXCEPTION
AUX. 1 LED
OFF
ON
ON
OFF
FACEPLATE
MODBUS READ EXCEPTION
AUX. 1 LED
OFF
ON
ON
OFF
STATUS
00H
40H
40H
00H
00H
STATUS
00H
44H
44H
00H
STATUS
00H
40H
40H
00H