SETPOINTS MODE
Setpoint Name
Analog In Alarm
Analog In Alarm Delay
Analog In Alarm Relay
6. Analog Output setpoints.
Analog Output Parameter
Analog Output Range:
7. Communication setpoints.
Relay Address
Baud Rate
8. Calibration Mode setpoints.
Exercise Relay
(Status of Switch Inputs)
LCD Display Contrast
9. Voltage setpoints.
VT Connection
VT Nominal Sec Volts
VT Primary Volts
Zero Volts Detect
Undervolt Trip
Undervolt Trip Level
Undervolt Trip Delay
Undervolt Trip Relay
Undervolt Alarm
Undervolt Alarm Level
Undervolt Alarm Delay
Undervolt Alarm Relay
Overvolt Trip
Overvolt Trip Level
Overvolt Trip Delay
Overvolt Trip Relay
Overvolt Alarm
Overvolt Alarm Level
Overvolt Alarm Delay
Overvolt Alarm Relay
10. Demand Metering setpoints.
Amps Demand
Amps Demand Time Period
Amps Demand Alarm
Amp Demand Alarm Level
5-8
Factory Setpoint
12.00.
1 Sec.
Aux1. (Aux2 for 575)
Phase A Current.
4-20 mA.
1.
2400 BAUD.
Trip.
5.
Wye.
120 Volts.
1.2 kV.
Disabled.
Disabled.
80% VT
1.0 Sec.
Trip & Aux1.
Disabled.
85% VT
1.0 Sec.
Aux2.
Disabled.
120% VT
1.0 Sec.
Trip. (Trip&Aux1 for 575)
Disabled.
115% VT
1.0 Sec.
Aux1. (Aux2 for 575)
Enabled.
5 Min.
Disabled.
100 A.
Range
Min Curr Scale Value to Max Curr Scale Value
1 to 255 sec
Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
Phase A Current, Phase B Current, Phase C Current,
Ground Current, Phase A-X Voltage, Phase B-X Voltage,
Phase C-X Voltage, Feeder Frequency, and External
Analog Select
0-1mA or 4-20mA
1 to 254
1200, 2400, 4800, and 9600 Baud
Trip, Aux1, Aux2, Aux3, and All (565)
Trip, Aux1, Aux2, Aux3, Aux4, Block Tap Changer, and
All (575)
0 to 10
Wye, Open Delta, Delta/Wye and None
48 to 240 Volts
0.1 to 69 kV
Enabled/Disabled
Enabled/Disabled
50 to 100%
0.1 to 25.5 sec
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Enabled/Disabled
50 to 100%
0.1 to 25.5 sec
Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Enabled/Disabled
101 to 125%
0.1 to 25.5 sec
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Enabled/Disabled
101 to 125%
0.1 to 25.5 sec
Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
Enabled/Disabled
5 to 120 Min
Enabled/Disabled
10 to 5000 A
Step
1 sec
1
1
0.01 kV
1%
0.1 sec
1%
0.1 sec
1%
0.1 sec
1%
0.1 sec
1 Min
5 A