GE Multilin 565 Instruction Manual page 11

Feeder management relay
Table of Contents

Advertisement

Table 2-1 - Terminal Identification
Terminal
Function
1
Ext. Switch #1 "+"
2
Ext. Switch #2 "+"
3
Ext. Switch #3 "+"
4
Ext. Switch #4 "+"
5
Ext. Switch #5 "+"
6
Ext. Switch #6 "+"
7
Ext. Switch #7 "+"
8
Ext. Switch #8 "+"
9
Breaker Open (52b) "+"
10
Breaker Common "–"
11
Breaker Closed (52a) "+"
12
Reclosure Enable "+"
13
Reclosure Common "–"
14
Reclosure Disable "+"
15
Block TC Common
16
Block TC N.O.
17
Analog Out "-"
18
Analog Out "+"
19
Analog Select A
20
Analog Select B
21
Analog Select C
22
Analog Select D
23
Analog In "-"
24
Analog In "+"
25
Trip Relay N.C.
26
Remote Trip "+"
27
Remote Common "-"
28
Remote Close "+"
29
Block TC N.C.
30 **
Aux 4 Relay N.O.
31 **
Aux 4 Relay Common
32 **
Aux 4 Relay N.C.
33 **
Access Switch "+"
34 **
Access Switch "-"
35
Voltage Input V1
36
Voltage Input V2
** 565 requires Option Card
Terminal
}
575 only
575 only
Function
37
Voltage Input V3
38
Voltage Input Vn
39
43 Remote "+"
40
43 Remote "-"
41
Trip Relay N.O.
42
Close Relay Contact 1
43
Aux 1 Relay N.O.
44
Aux 2 Relay N.O.
45
Aux 3 Relay N.C.
46
Aux 1 Relay N.C.
47
Aux 2 Relay N.C.
48
Aux 3 Relay N.O.
49
Phase 1 Common
50
Phase 1 Input :5/:1
51
Phase 2 Common
52
Phase 2 Input :5/:1
53
Phase 3 Common
54
Phase 3 Input :5/:1
55
Ground Current Common
56
Ground Current Input :5/:1
57
Trip Relay Common
58
Close Relay Contact 2
59
Aux 1 Relay Common
60
Aux 2 Relay Common
61
Aux 3 Relay Common
62
Control Voltage GND
63
Supply Voltage "+"
64
Supply Voltage "-"
65
RS485 Port "+"
66
RS485 Port "-"
67
MTM/RS485 Shield
68 **
MTM RS485 "+"
69 **
MTM RS485 "-"
70
IRIG-B
71
Analog Select Common
72
Ext. Switch Common
INSTALLATION
575 only
2-7

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 565 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Related Products for GE Multilin 565

This manual is also suitable for:

575

Table of Contents

Save PDF