Installation Guide

6.6 Flow / power limit

Application A230.2:
A flow or heat meter can be connected to the ECL controller in
order to limit the flow or consumed power. The signal from the
flow or heat meter is a pulse signal.
When the flow / power gets higher than the set limit, the controller
gradually increases the desired flow temperature to obtain an
acceptable max. flow or power consumption.
Actual (actual flow or power)
Circuit
1
The value is the actual flow or power based on the signal from flow / heat
meter, converted in the controller.
Limit (limitation value)
Circuit
1
Set the limitation value.
80
DEN-SMT/DK
ECL Comfort 210, application A230
11110
Factory setting
Setting range
Read-out only
11111
Setting range
Factory setting
0.0 ... 999.9 l/h
999.9 l/h
Desired flow temperature
Limit
Flow / power
limitation
Desired flow
temp.
If the 'Adapt. time' is too high, there is a risk of unstable control.
VI.LG.H1.02
Flow / power
Limit
Time