Infl. — max.
Circuit
1
If the wind speed is higher than the set value in 'Limit' , the desired flow
temperature will be increased by the number of degrees per 1 m/s.
Filter constant
Circuit
1
The filter constant dampens the wind speed input data by the set factor.
1:
No filtering.
2:
Fast (low filter constant)
50:
Slow (high filter constant)
58
DEN-SMT/DK
ECL Comfort 210, application A230
11057
Setting range
Factory setting
0.0 ... 9.9
0.0
11081
Factory setting
Setting range
1 ... 50
Example:
The wind limit is active at wind speed higher than 10 m/s.
The max. influence is set to 2.0.
The actual wind speed is 2 m/s over limit.
Result:
The desired flow temperature is increased by 2.0 × 2 = 4.0 degrees.