Installation Guide
2.5.2 Electrical connections, 230 V a.c., power supply, pumps, motorized control valves etc.
Application A230
Terminal
Description
16
Alarm (only application A230.1)
15
14
Phase for circulation pump
13
Do not use
12
P2
P2 Relay operated by schedule 2
11
P1
Circulation pump ON / OFF
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
M1
Phase for motorized control valve output
7
M1
Actuator - opening 0.2 A / 230 V a.c.
6
M1
Actuator - closing 0.2 A / 230 V a.c.
5
Do not use
4
Do not use
3
Do not use
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14 , L to 5 and L to 9, N to 10
16
DEN-SMT/DK
ECL Comfort 210, application A230
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
VI.LG.H1.02
Max. load
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.