Danfoss ECL Comfort 210 Installation Manual page 81

Application a230
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Adapt. time (adaptation time)
Circuit
1
Controls how fast the flow / power limitation adapts to the desired
limitation.
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted slowly.
50:
The desired temperature is adapted quickly.
Filter constant
Circuit
1
The filter constant dampens the flow / power input data by the set factor.
1:
No filtering.
2:
Fast (low filter constant)
50:
Slow (high filter constant)
Input type
Circuit
1
Choice of pulse type from input S7.
OFF:
No input.
IM1:
Pulse.
Danfoss District Energy
ECL Comfort 210, application A230
11112
Setting range
Factory setting
OFF / 1 ... 50 s
OFF
11113
Setting range
Factory setting
1 ... 50
11109
Setting range
Factory setting
OFF / IM1
OFF
10
VI.LG.H1.02
DEN-SMT/DK
81