5.0 Settings, application A230.1

5.1 Flow temperature

APPLICATION A230.1:
The ECL Comfort controller determines and controls the flow
temperature related to the outdoor temperature. This relationship
is called the heat curve.
The heat curve is set by means of 6 coordinate points. The desired
flow temperature is set at 6 pre-defined outdoor temperature
values.
The shown value for the heat curve is an average value (slope),
based on the actual settings.
Outdoor
Desired flow temp.
temp.
A
-30 °C
45 °C
-15 °C
40 °C
-5 °C
35 °C
0 °C
32 °C
5 °C
30 °C
15 °C
25 °C
Adjust the desired flow temperature at -30, -15, -5, 0, 5, and 15 °C,
if required.
A: Example for floor heating
B: Factory settings
C: Example for radiator heating (high demand)
Heat curve
Circuit
1
Push the dial to enter / change the coordinates of the heat curve.
The heat curve represents the desired flow temperatures at
different outdoor temperature and at a desired room temperature
of 20 °C.
If the desired room temperature is changed, the desired flow
temperature also changes:
(Desired room T - 20) × HC × 2.5
where "HC" is the Heat Curve slope and "2.5" is a constant.
Danfoss District Energy
ECL Comfort 210, application A230
Your
settings
B
C
75 °C
95 °C
60 °C
90 °C
50 °C
80 °C
45 °C
70 °C
40 °C
60 °C
28 °C
35 °C
Factory setting
Setting range
Read-out only
Desired flow temperature
110
100
B
80
60
A
40
20
-50 -40 -30 -20 -10
The calculated flow temperature can be influenced by the 'Boost' and
'Ramp' functions etc.
Example:
Heat curve:
Desired flow temp.:
Desired room temp.:
Calculation (22–20) × 0.7 × 2.5 =
Result:
The desired flow temperature will be corrected from 50 °C to 53.5 °C.
VI.LG.H1.02
0
10
20
0.7
50 °C
22 °C
3.5
DEN-SMT/DK