Table of Contents

Advertisement

Installation Guide

4.0 Settings overview

It is recommendable to make a note of any changed settings in the empty columns.
Setting
APPLICATION A230.1:
Heat curve
Temp. max. (flow temp. limit, max.)
Temp. min. (flow temp. limit, min.)
Adapt. time (adaption time)
Infl. - max. (room temp. limitation, max.)
Infl. - min. (room temp. limitation, min.)
High T out X1 (return temp. limitation, high limit, X-axis)
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Low T out X2 (return temp. limitation, low limit, X-axis)
High limit Y2 (return temp. limitation, high limit, Y-axis)
Infl. - max. (return temp. limitation - max. influence)
Infl. - min. (return temp. limitation - min. influence)
Adapt. time (adaptation time)
Priority (priority for return temp. limitation)
High T out X1 (flow / power limitation, high limit, X-axis)
Low limit Y1 (flow / power limitation, low limit, Y-axis)
Low T out X2 (flow / power limitation, low limit, X-axis)
High limit Y2 (flow / power limitation, high limit, Y-axis)
Adapt. time (adaptation time)
Filter constant
Input type
Units
Pulse
Wind actual
Limit
Infl. — max.
Filter constant
Auto saving (saving temp. dependent on outdoor temp.)
Boost
Ramp (reference ramping)
Optimizer (optimizing time constant)
Pre-stop (optimized stop time)
Based on (optimization based on room / outdoor temp.)
Total stop
Cut-out (limit for heating cut-out)
Motor pr. (motor protection)
Xp (proportional band)
Tn (integration time constant)
M run (running time of the motorized control valve)
Nz (neutral zone)
44
DEN-SMT/DK
ECL Comfort 210, application A230
ID
11178
11177
11015
11182
11183
11031
11032
11033
11034
11035
11036
11037
11085
11119
11117
11118
11116
11112
11113
11109
11115
11114
11099
11057
11081
11011
11012
11013
11014
11026
11020
11021
11179
11174
11184
11185
11186
11187
Page
Factory settings in circuit(s)
1
2
47
47
48
90 °C
48
10 °C
49
25 s
50
-4.0
50
0.0
51
15 °C
51
40 °C
51
-15 °C
52
60 °C
52
0.0
52
0.0
52
25 s
53
OFF
54
15 °C
999.9
55
l/h
55
-15 °C
999.9
55
l/h
55
OFF
55
10
56
OFF
56
ml, l/h
56
10
57
57
10.0 m/s
58
0.0
58
10
59
-15 °C
59
OFF
60
OFF
60
OFF
61
ON
61
OUT
61
OFF
62
18 °C
63
OFF
63
80 K
63
30 s
63
60 s
64
3 K
VI.LG.H1.02
3