Cut-out (limit for heating cut-out)
Circuit
1
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
This function can save energy.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
62
DEN-SMT/DK
ECL Comfort 210, application A230
11179
Setting range
Factory setting
OFF / 1 ... 50 °C
18 °C
Temp.
Actual outdoor temp.
18 °C
Heating ON
Heating OFF
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
VI.LG.H1.02
Accumulated outdoor temp.
Time
Heating ON
Danfoss District Energy