Infl. - min. (compensation temp., 2. point)
Circuit
1
Determines how much the desired flow temperature will be influenced if the
compensation temperature is lower than the set limit.
Influence higher than 0:
The desired flow temperature is increased, when the compensation
temperature gets below the set limit.
Influence lower than 0:
The desired flow temperature is decreased, when the compensation
temperature gets below the set limit.
Combination of two compensation temperatures:
Regarding compensation temperatures, the example shows that
below Comp. 1 and above Comp. 2, the desired flow temperature
will be increased, but with different values.
Comp. 1 value is set to 21 °C and Comp. 2 value is set to 25 °C.
'Infl. min.' for Comp. 1 is set to 2.5 and 'Infl. max.' for Comp. 1 is
set to 0.0.
'Infl. min.' for Comp. 2 is set to 0.0 and 'Infl. max.' for Comp. 2 is
set to 1.5.
The desired flow temperature is kept on a constant level as long
as the compensation temperature is between 21 and 25 °C, but
the desired flow temperature will rise if the the compensation
temperature gets above 25°C or below 21°C.
Danfoss District Energy
ECL Comfort 210, application A230
11067
Setting range
Factory setting
-9.9 ... 9.9
0.0
Example
The limit value is set to 25 °C.
'Infl. min. ' is set to 0.5.
The actual compensation temperature is 23 °C (2 degrees below the
limit value).
Result:
The desired flow temperature is changed by 0.5 x 2= 1.0 degree.
Influence
Comp. 1
Comp. 2
VI.LG.H1.02
Temp. S1
DEN-SMT/DK