2.5.3 Electrical connections, safety thermostats, 230 V a.c. or 24 V a.c.
With safety thermostat:
2.5.4 Electrical connections, application 230.2 with 2 circulation pumps in sequence, controlled by schedule 2
Terminal
Description
14
Do not use
13
P2
Circulation pump 2 ON / OFF
12
P1
Circulation pump 1 ON / OFF
11
Phase for circulation pump control
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14 , L to 5 and L to 9, N to 10
Danfoss District Energy
ECL Comfort 210, application A230
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
VI.LG.H1.02
Max. load
4 (2) A / 230 V a.c.*