Min. act. time (min. activation time gear motor)
Circuit
1
The min. pulse period of 20 ms (milliseconds ) for activation of the gear
motor.
Setting example
2
10
50
Danfoss District Energy
ECL Comfort 210, application A230
11189
Setting range
Factory setting
2 ... 50
Value x 20 ms
40 ms
200 ms
1000 ms
The setting should be kept as high as acceptable to increase the
10
lifetime of the actuator (gear motor).
VI.LG.H1.02
DEN-SMT/DK
87